Performance features
- External sensor for the gas detectors GX-A1 and GX-HS
- Detection of carbon monoxide (CO) or smoke
- is also installed on the gas detector GX-C2
- Catalytic sensor with high cross-sensitivities for a broad spectrum
- is connected to the cable via an RJ connector
The connecting cable of the sensor can be extended. The following minimum cross-sections apply depending on the length of the cable
on the length of the cable:
Cable cross section 3 x 0.75 mm²: maximum length 10 m
Cable cross section 3 x 1.5 mm²: maximum length 20 m
Scope of delivery
- Gas sensor GX-CO
- Instructions for use
- Mounting material
Technical data
Operating voltage: | 5 V +/- max. 0.1 Volt |
Sensor type | catalytic |
Trigger concentration | 80 - 200 ppm = approx. 2.5 V, depending on temperature |
Humidity (ambient) | 5-90 % RH (non-condensing) |
Functional area | -10 °C / +40 °C |
Storage temperature | -20 °C / +50 °C |
Lifetime | depending on ambient conditions Observe test date |
Protection class | IP 20 for dry indoor areas only |
Cable length | 2,5 m |
Cable Ø | 3.5 mm / 3×0.14 mm² |
Dimensions (HxWxD) | 52x27x29 mm |
Current consumption | 300 mA @ 5V |
Sensitivity characteristic
to ethanol vapor and various other gases and vapors. The sensor has different characteristics for each gas or vapor. The GX-CO is very sensitive to organic solvent vapors and alcohols.
WEEE NO.: EN91394868